{{ $t('shop.all.spaetbestellservice.hinweis') }}
Dimensions W x L x H | 50 mm x 107 mm x 55 mm |
Device specific diagnosis |
Diagnose-Speicher, Kanal- und modulorientierte Diagnose, Unterspannung/Kurzschluss Module |
CPU data |
32 MB flash, 256 MB RAM, Processor 800 Hz |
Configuration support | CODESYS V3 |
Parameterising | CODESYS V3 |
Total number of axes | 31 |
Additional functions |
Diagnose functions, Softmotion functions for electrical actuator |
Operating element |
Rotary switch for RUN/Stop, DIL switch for CAN connection |
Programming, operating language | DE, EN |
Programming, support file handling | yes |
Processing time | approx. 200 µs/1 k instruction |
Intrinsic power input at operating voltage | type 85 mA |
Setting IP address |
DHCP, over MMI, over CoDeSys |
Functional building block |
CPX diagnosis status, CPX copy diagnosis trace, CPX read module diagnosis, and other |
Marker |
Variable concept CoDeSys, 28 kB residual data |
Nominal operating voltage DC load voltage |
24 V, With pneumatic type Midi/Maxi: 21.6 ... 26.4V, With pneumatic type CPA: 20.4 ... 26.4V, With pneumatic type MPA: 18 ... 30V, Without pneumatic: 18 ... 30V |
Nominal operating voltage DC [V] | 24 |
Power blackout bridging [ms] | 10 |
Programming software | CODESYS provided by Festo |
Programming language |
Instruction list (AWL), Contact diagram (KOP), acc. to IEC 61131-3, Sequence language, Function plan, Structured text, Additional CFC |
Programming memory | 16 MB user program |
Corrosion resistant class KBK | 2 - moderate corrosion stress |
Bearing temperature [°C] | -20 to 70 |
Relative humidity |
95 %, Not condensing |
Protection category |
IP65, IP67 |
ambient temperature [°C] | -5 to 50 |
Product weight [g] | 135 |
Ethernet, number | 1 |
Ethernet, data transfer speed | 10/100 Mbit/s |
Ethernet supported protocols | TCP/IP, EasyIP, Modbus TCP |
Ethernet, connection plug |
RJ45, 8 pin, Bushing |
Fieldbus interface, galvanically separated | yes |
Fieldbus interface, transfer rate |
125, 250, 500, 800, 1000kbit/s, can be set via software |
Fieldbus interface, connection technology |
Sub-D, 9 pin, Plug |
Fieldbus interface | CAN bus |
Report |
CODESYS Level 2, EasyIP, Modbus TCP, TCP/IP |
Control interface | CAN bus |
Ethernet interface | RJ 45 (jack, 8-pin) |
LED display bus specific | TP: Link / traffic |
LED display product specific |
ERR: Runtime error PLC, M: Modify/force active, PL: Load supply, RUN: PLC status, SF: System error, STOP: PLC status, PS: Electronics supply, sensor supply |
Material information | RoHs compliant |
Housing material |
PC, PA reinforced |
{{ $t('shop.all.gewicht') }} | 135 g / ks |
{{ $t('shop.display.artikel.zollwarennummer') }} | 85371091 |
{{ $t('shop.all.hersteller') }} | Festo |